2600 Family Instruction Manual
Chapter 5 : Common IOM Actions
5.2.3 ResetFlags
Function Resets to zero the specified bit flags in the Status
byte.
Opcode 0xF2
Command (BitMask)
Response none
Notes This action clears all of the specified bit flags in
the Status byte (Section 3.4.1), which is present
in every ModRsp.
Except for the HRST (hard reset) bit flag, any
combination of bit flags may be cleared by the
Ethernet client. The client is not permitted to
clear the HRST flag because this flag is reserved
for gateway-to-IOM link control.
5.2.4 SetWatchdog
Function Programs the communication watchdog time-out
interval.
Opcode 0xF3
Command (Interval)
Response none
Notes The communication watchdog timer is used to
detect interruptions in communications between
the gateway and IOM. If no communications are
received from the gateway within the specified
time-out interval, an IOM will execute a
hardware watchdog reset. This behavior ensures
the shutdown of all I/O on any IOM which has
lost communication with the gateway.
The gateway automatically invokes this action
for an IOM when it first establishes
communication with the module. As a result,
there is no need for the client to explicitly invoke
this action. In a typical application system, the
client will never need to, nor should it, invoke
this action.
5.2.5 GetProductID
Function Returns the model type identifier.
Command (0xF5)
Response (ModelNum<15:8>),(ModelNum<7:0>)
Notes The returned value is a 16-bit, unsigned integer
that indicates the model number of the target
module. For example, the decimal value 2650 is
returned by a model 2650 relay module.
5.2.6 GetVersion
Function Returns the firmware version number.
Opcode 0xF6
Command none
Response (MajorVer),(MinorVer)
Notes On firmware labels, the major and minor version
numbers are printed with a decimal point
delimiter. For example, printed version “1.02” is
indicated by MajorVer = 1 and MinorVer =
2.
5.2.7 GetAddress
Function Returns the address shunt settings.
Opcode 0xF7
Command none
Response (Address)
Parameter Function
BitMask Specifies the bit flags to be cleared. Set
a mask bit to one to clear the matching
Status bit. Set a mask bit to zero to
leave the matching Status bit in its
current state.
Parameter Function
Interval Communication watchdog interval,
specified in 2 millisecond increments.
Specify zero to disable the
communication watchdog.
Parameter Function
ModelNum Model number of the target module.
Parameter Function
MajorVer Major version number. Ranges from
00 to 99 decimal.
MinorVer Minor version number. Ranges from
00 to 99 decimal.
Parameter Function
Address Address shunt settings. Ranges from
0x00 to 0x0F.