Sensoray 2600 Manual do Utilizador Página 58

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 80
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 57
2600 Family Instruction Manual
53
Chapter 9 : Model 2620 Counter Module
XC: Index source:
0 - External Index pin.
1 - Internal free-running gate generator.
Response none
Notes After the mode is changed to its target value, the
counter core is automatically reset to zero. The
channel’s preload registers are not changed by
this action.
The target channel’s mode changes immediately
to the specified mode when the SetMode action
executes. As a result, the client may invoke
another action that will modify the counter core
(i.e., SetCounter) immediately after a
SetMode action.
9.4.2 SetCommonControl
Function Programs the gate time divisor and time stamp
resolution common to all counter channels.
Opcode 0x0F
Command (Ctrl<7:0>),(Ctrl<15:8>)
Ctrl is a 16-bit value, passed LSB first, that is
composed of two bit fields that specify the gate
time divisor (G) and time stamp resolution (TS).
These values are common to all counter channels.
Figure 47: Ctrl MSB
Figure 48: Ctrl LSB
G: Gate time divisor (14-bit field):
2 to 16,383 - Specifies the gate time divisor
that is common to all channels. The gate
interval is set to 2*(G+1) milliseconds; this
is the period of the square-wave output
produced by the gate generator.
TS: Time stamp resolution (2-bit field):
0 - 1 microsecond.
1 - 10 microseconds.
2 - 100 microseconds.
3 - 1 millisecond.
Response none
Notes This action does not require a counter channel
number to be attached to the opcode byte.
When using the time gate in frequency counter
applications, set the gate time divisor so that the
gate generator period equals the desired gate
time. For example, set the gate time divisor to
499 to generate a one-second gate period.
The time stamp resolution should be programmed
so as to meet the needs of the channel having the
highest resolution; all other channels must then
use the same time stamp resolution.
The application must trade-off time stamp
resolution for longer time stamp intervals, as
shown in the following table:
9.4.3 SoftTrigger
Function Triggers counter latch and/or load.
Opcode 0x01 + Chan * 16
Command (Flags)
Flags contains bits that specify the action or
actions that are being triggered.
LAT: Transfer counter core to data latch.
LOD: Force counter load from a preload register.
If only one preload register is in use, Preload0 is
always used. If both preload registers are in use,
the active preload register will be used and the
register pointers will be toggled so that the other
preload register will be used next time.
Response none
Parameter Function
Ctrl Common counter configuration values.
15
G13
14
G12
13
G11
12
G10
11
G9
10
G8
9
G7
8
G6
7
G5
6
G4
5
G3
4
G2
3
G1
2
G0
1
TS1
0
TS0
Resolution Maximum Interval
1 µs 65.536 ms
10 µs 655.36 ms
100 µs 6.5536 seconds
1 ms 65.536 seconds
Parameter Function
Flags Bits that specify the soft trigger actions
that are being invoked.
7
0
6
0
5
0
4
0
3
0
2
0
1
LAT
0
LOD
Vista de página 57
1 2 ... 53 54 55 56 57 58 59 60 61 62 63 ... 79 80

Comentários a estes Manuais

Sem comentários