These API functions write to SWE protected registers:
S826_DacRangeWrite and S826_DacDataWrite (when safemode argument = '1')
S826_DioOutputSourceWrite, S826_DioSafeWrite, and S826_DioSafeEnablesWrite
S826_WatchdogConfigWrite, S826_WatchdogEnableWrite
S826_SafeControlWrite
S826_VirtualSafeWrite and S826_VirtualSafeEnablesWrite
10.2 Programming
10.2.1 S826_SafeControlWrite
The S826_SafeControlWrite function programs the board's fail-safe configuration and state.
int S826_SafeControlWrite(
uint board, // board identifier
uint settings, // safemode settings
uint mode // write mode
);
Parameters
board
826 board number. This must match the settings of the board's dip switches as described in section 2.2.
settings
Safemode configuration and state bits:
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 XSF 0 SAF 0
Bit Function
XSF DIO47 trigger enable. Programmed to '0' upon reset.
When '1', a low level (0 volts) on the DIO channel 47 header pin will set the SAF bit. When '0', DIO47 will not affect
the SAF bit. When XSF=1, a thread can block on DIO47 falling edge events to receive notification when safemode is
triggered. Alternatively,the program can poll SAF.
SAF Safemode state. Programmed to '0' upon reset.
'1' = safemode active, '0' = runmode active. This can be written by the application program. This bit can also be set by
DIO47 when XSF=1, or by a timeout event on watchdog Timer0.
mode
Write mode: 0 = write, 1 = clear bits, 2 = set bits (see “Atomic Read-Modify-Write”).
Return Values
If the function succeeds, the return value is zero.
If the function fails, the return value is an error code.
Remarks
This function should only be called when the SWE bit is set (see S826_SafeWrenWrite). The function will fail without
notification (return S826_ERR_OK) if SWE=0 (see Section 10.1.1).
10.2.2 S826_SafeControlRead
The S826_SafeControlRead function returns the board's fail-safe configuration and state.
826 Instruction Manual 67 Safemode Controller